EasyManua.ls Logo

ABB RET670 - Page 780

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Name Values (Range) Unit Step Default Description
V2LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V2AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
V2AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
V2AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
UAmpPreComp5 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
5% of Ir
UAmpPreComp30 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
30% of Ir
UAmpPreComp100 -10.000 - 10.000 % 0.001 0.000 Amplitude factor to pre-calibrate voltage at
100% of Ir
Table 226: VMSQI Non group settings (advanced)
Name Values (Range) Unit Step Default Description
3V0ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3V0HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
3V0HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
3V0LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
3V0LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
V1ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
V1HiHiLim 0.000 -
10000000000.000
V 0.001 260000.000 High High limit (physical value)
V1HiLim 0.000 -
10000000000.000
V 0.001 240000.000 High limit (physical value)
V1LowLim 0.000 -
10000000000.000
V 0.001 220000.000 Low limit (physical value)
V1LowLowLim 0.000 -
10000000000.000
V 0.001 200000.000 Low Low limit (physical value)
V1AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
V1AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
V1AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
V1AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table continues on next page
Section 3 1MRK504116-UUS C
IED application
774
Application manual

Table of Contents

Other manuals for ABB RET670