Table 225: VMSQI Non group settings (basic)
Name Values (Range) Unit Step Default Description
3V0DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
3V0Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
3V0Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
3V0RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
3V0LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
3V0AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
3V0AngZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
3V0AngMin -180.000 - 180.000 Deg 0.001 -180.000 Minimum value
3V0AngMax -180.000 - 180.000 Deg 0.001 180.000 Maximum value
3V0AngRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V1DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V1Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V1Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V1RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
V1LimHys 0.000 - 100.000 % 0.001 5.000 Hysteresis value in % of range and is
common for all limits
V1AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
V2Min 0.000 -
10000000000.000
V 0.001 0.000 Minimum value
V2Max 0.000 -
10000000000.000
V 0.001 300000.000 Maximum value
V2RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Table continues on next page
1MRK504116-UUS C Section 3
IED application