Name Values (Range) Unit Step Default Description
DefaultScreen 0 - 0 - 1 0 Default screen
EvListSrtOrder Latest on top
Oldest on top
- - Latest on top Sort order of event list
SymbolFont IEC
ANSI
- - IEC Symbol font for Single Line Diagram
3.3.3 Indication LEDs
3.3.3.1 Introduction
The function block LEDGEN controls and supplies information about the status of the
indication LEDs. The input and output signals of LEDGEN are configured with
PCM600. The input signal for each LED is selected individually with the Signal
Matrix Tool in PCM600.
LEDs (number 1–6) for trip indications are red.
LEDs (number 7–15) for pickup indications are yellow.
Each indication LED on the local HMI can be set individually to operate in six
different sequences
Two sequences operate as follow type.
Four sequences operate as latch type.
Two of the latching sequence types are intended to be used as a protection
indication system, either in collecting or restarting mode, with reset
functionality.
Two of the latching sequence types are intended to be used as signaling
system in collecting (coll) mode with an acknowledgment functionality.
The light from the LEDs can be steady (-S) or flashing (-F). See the technical reference
manual for more information.
1MRK504116-UUS C Section 3
IED application
71
Application manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals