• IEDProdType
• ProductDef
• FirmwareVer
• SerialNo
• OrderingNo
• ProductionDate
The settings are visible on the local HMI , under Main menu/Diagnostics/IED status/
Product identifiers
They are very helpful in case of support process (such as repair or maintenance).
3.4.7.2 Setting parameters
The function does not have any parameters available in the local HMI or PCM600.
Factory defined settings
The factory defined settings are very useful for identifying a specific version and very
helpful in the case of maintenance, repair, interchanging IEDs between different
Substation Automation Systems and upgrading. The factory made settings can not be
changed by the customer. They can only be viewed. The settings are found in the local
HMI under Main menu/Diagnostics/IED status/Product identifiers
The following identifiers are available:
• IEDProdType
• Describes the type of the IED (like REL, REC or RET). Example: REL670
• FirmwareVer
• Describes the firmware version. Example: 1.4.51
• Firmware versions numbers are “running” independently from the release
production numbers. For every release numbers (like 1.5.0.17) there can be
one or more firmware versions, depending on the small issues corrected in
between releases.
• IEDMainFunType
• Main function type code according to IEC 60870-5-103. Example: 128
(meaning line protection).
• SerialNo
• OrderingNo
• ProductionDate
3.4.8 Rated system frequency PRIMVAL
1MRK504116-UUS C Section 3
IED application
85