Setting of timers for distance protection zones
The required time delays for different distance protection zones are independent of
each other . Distance protection zone 1 can also have a time delay, if so required for
selectivity reasons. Time delays for all zones can be set in a range of 0 to 60 seconds.
The tripping function of each particular zone can be inhibited by setting the
corresponding Operation parameter to Disabled. Different time delays are possible for
the phase-to-ground tLG and for the phase-to-phase tPP measuring loops in each
distance protection zone separately, to further increase the total flexibility of a distance
protection.
3.6.1.4 Setting parameters
Signals and settings for ZMQPDIS are valid for zone 1 while signals
and settings for ZMQAPDIS are valid for zone 2 - 5
Table 49: ZMQPDIS (21) Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Enabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base current, i.e. rated current
VBase 0.05 - 2000.00 kV 0.05 400.00 Base voltage, i.e. rated voltage
OperationDir Disabled
Non-directional
Forward
Reverse
- - Forward Operation mode of directionality NonDir /
Forw / Rev
X1 0.10 - 3000.00 ohm/p 0.01 30.00 Positive sequence reactance reach
R1 0.01 - 1000.00 ohm/p 0.01 5.00 Positive seq. resistance for zone
characteristic angle
X0 0.10 - 9000.00 ohm/p 0.01 100.00 Zero sequence reactance reach
R0 0.01 - 3000.00 ohm/p 0.01 15.00 Zero seq. resistance for zone characteristic
angle
RFPP 0.10 - 3000.00 ohm/l 0.01 30.00 Fault resistance reach in ohm/loop, Ph-Ph
RFPG 0.10 - 9000.00 ohm/l 0.01 100.00 Fault resistance reach in ohm/loop, Ph-G
OperationPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Phase loops
Timer tPP Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Zone
timer, Ph-Ph
tPP 0.000 - 60.000 s 0.001 0.000 Time delay of trip, Ph-Ph
OperationPG Disabled
Enabled
- - Enabled Operation mode Disable/Enable of Phase-
Ground loops
Timer tPG Disabled
Enabled
- - Enabled Operation mode Disable/ Enable of Zone
timer, Ph-G
Table continues on next page
1MRK504116-UUS C Section 3
IED application
187
Application manual