Name Values (Range) Unit Step Default Description
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of
In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30%
of In
IMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 100%
of In
VMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 5% of
Vn
VMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 30%
of Vn
VMagComp100 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate voltage at 100%
of Vn
IAngComp5 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 5% of In
IAngComp30 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 30% of In
IAngComp100 -10.000 - 10.000 Deg 0.001 0.000 Angle calibration for current at 100% of In
Table 112: GUPPDUP (37) Non group settings (basic)
Name Values (Range) Unit Step Default Description
IBase 1 - 99999 A 1 3000 Base setting for current level
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage level
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - Pos Seq Selection of measured current and voltage
3.7.11 Directional overpower protection GOPPDOP (32)
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Directional overpower protection GOPPDOP
P >
DOCUMENT172362-IMG158942
V1 EN
32
Section 3 1MRK504116-UUS C
IED application
484
Application manual