EasyManua.ls Logo

ABB RET670 - Setting Guidelines

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
recordings. The disturbance recording information is included in the disturbance
recorder files, which may be uploaded to PCM600 for further analysis using the
Disturbance Handling tool. The information is also available on a station bus according
to IEC 61850 and according to IEC 60870-5-103.
3.15.11.2 Setting guidelines
The setting parameters for the Disturbance Recorder function (DR) is a part of the
Disturbance Report settings.
It is possible to handle up to 40 analog and 96 binary signals, either internal signals or
signals coming from external inputs. The binary signals are identical with the signals
recorded by the other functions in the Disturbance Report function, that is Event
recorder (ER), Indication (IND) and Trip value recorder (TVR) function.
For the DR function there is one dedicated setting:
OperationM: Analog channel M is to be recorded by the disturbance recorder (On) or
not (Off). Other disturbance report settings, such as Operation and TrigLevel for binary
signals, will also influence the disturbance recorder.
3.16 Metering
3.16.1 Pulse-counter logic PCGGIO
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse-counter logic PCGGIO
S00947 V1 EN
-
3.16.1.1 Application
Pulse counter logic function counts externally generated binary pulses, for instance
pulses coming from an external energy meter, for calculation of energy consumption
values. The pulses are captured by the binary input module (BIM), and read by the
pulse counter function. The number of pulses in the counter is then reported via the
station bus to the substation automation system or read via the station monitoring
Section 3 1MRK504116-UUS C
IED application
802
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals