Therefore simple logic can be created in the Application Configuration tool to detect
such CB behavior. Such CB condition can be just alarmed, and if required, the built in
disturbance recorder can also be triggered.
To create this logic, a binary signal that the CB is going to be opened (but not trip
command) shall be made available to the IED.
3.7.13.3 Setting parameters
Table 119: CBPGAPC Group settings (basic)
Name Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Operation Enable/Disable
IBase 1 - 99999 A 1 3000 Rated capacitor bank current
OperationRecIn Disabled
Enabled
- - Enabled Operation reconnection inhibit enable/disable
IRecInhibit 4 - 1000 %IB 1 10 Cap bank cut off current level for inhibit in %
of IBase
tReconnInhibit 1.00 - 6000.00 s 0.01 300.00 Time delay for reconnected inhibit signal
OperationOC Disabled
Enabled
- - Enabled overcurrent enable/disable
PU 51 0 - 900 %IB 1 135 Pick up level for overcurrent in % of Ibase
tOC 0.00 - 6000.00 s 0.01 30.00 Time delay for overcurrent operation
Operation37 Disabled
Enabled
- - Disabled Operation of undercurrent element enable/
disable
PU_37 5 - 100 %IB 1 70 Pick up level for undercurrent element in % of
Ibase
tUC 0.00 - 6000.00 s 0.01 5.00 time delay for undercurrent operation
Operation QOL Disabled
Enabled
- - Enabled Operation reactive power overload enable/
disable
UP _QOL 5 - 900 % 1 130 pick up for reactive power overload in %
tQOL 1.00 - 6000.00 s 0.01 60.00 Time delay for reactive power overload
operation
OperationHOL Disabled
Enabled
- - Enabled Operation harmonic over load enable/disable
HOL_DT_V 5 - 500 % 1 200 Pick up voltage for harmonic overload for DT
stage in %
tHOL_DT 0.00 - 6000.00 s 0.01 10.00 Time delay for minimum operation for
harmonic overload
PU_HOL_DT_V 80 - 200 % 1 110 pick up voltage for harmonic overload in
IDMT stage in %
k_HOL_IDMT 0.50 - 1.50 - 0.01 1.00 Time multiplier for harmonic overload IDMT
curve
tMax_HOL_IDMT 0.05 - 6000.00 s 0.01 2000.00 Maximum trip delay for harmonic overload
tmin_HOL_IDMT 0.05 - 60.00 s 0.01 0.10 Minimum trip delay for harmonic overload
1MRK504116-UUS C Section 3
IED application
501
Application manual