An example where VSGGIO is configured to switch Autorecloser enabled–disabled
from a button symbol on the local HMI is shown in figure 292. The Close and Open
buttons on the local HMI are normally used for enable–disable operations of the circuit
breaker.
IEC07000112-2-en_ansi.vsd
PSTO
CMDPOS12
IPOS1
NAM_POS1
NAM_POS2
IPOS2
CMDPOS21
Disabled
Enabled
VSGGIO
SMBRREC_79
ON
OFF
SETON
INTONE
INV
OUT
INPUT
ANSI07000112 V2 EN
Figure 292: Control of Autorecloser from local HMI through Selector mini switch
VSGGIO is also provided with IEC 61850 communication so it can be controlled from
SA system as well.
3.12.6.2 Setting guidelines
Selector mini switch (VSGGIO) function can generate pulsed or steady commands (by
setting the Mode parameter). When pulsed commands are generated, the length of the
pulse can be set using the tPulse parameter. Also, being accessible on the single line
diagram (SLD), this function block has two control modes (settable through CtlModel):
Dir Norm and SBO Enh.
3.12.6.3 Setting parameters
Table 174: VSGGIO Non group settings (basic)
Name
Values (Range) Unit Step Default Description
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
CtlModel Dir Norm
SBO Enh
- - Dir Norm Specifies the type for control model according
to IEC 61850
Mode Steady
Pulsed
- - Pulsed Operation mode
tSelect 0.000 - 60.000 s 0.001 30.000 Max time between select and execute signals
tPulse 0.000 - 60.000 s 0.001 0.200 Command pulse lenght