Name Values (Range) Unit Step Default Description
QRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
PFMin -1.000 - 1.000 - 0.001 -1.000 Minimum value
PFMax -1.000 - 1.000 - 0.001 1.000 Maximum value
PFRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
VMin 0.0 - 200.0 %VB 0.1 50.0 Minimum value in % of UBase
VMax 0.0 - 200.0 %VB 0.1 200.0 Maximum value in % of UBase
VRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IMin 0.0 - 500.0 %IB 0.1 50.0 Minimum value in % of IBase
IMax 0.0 - 500.0 %IB 0.1 200.0 Maximum value in % of IBase
IRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
FrMin 0.000 - 100.000 Hz 0.001 0.000 Minimum value
FrMax 0.000 - 100.000 Hz 0.001 70.000 Maximum value
FrRepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
Operation Disabled
Enabled
- - Disabled Disable/Enable Operation
IBase 1 - 99999 A 1 3000 Base setting for current values in A
VBase 0.05 - 2000.00 kV 0.05 400.00 Base setting for voltage value in kV
SBase 0.05 - 200000.00 MVA 0.05 2080.00 Base setting for power values in MVA
Mode A, B, C
Arone
Pos Seq
AB
BC
CA
A
B
C
- - A, B, C Selection of measured current and voltage
PowMagFact 0.000 - 6.000 - 0.001 1.000 Magnitude factor to scale power calculations
PowAngComp -180.0 - 180.0 Deg 0.1 0.0 Angle compensation for phase shift between
measured I & V
k 0.000 - 1.000 - 0.001 0.000 Low pass filter coefficient for power
measurement, V and I
Section 3 1MRK504116-UUS C
IED application
762