EasyManua.ls Logo

ABB RET670 - Page 191

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
1 2 1 2
1 2
0.8 1 0.2 1
arg Re
L L L L M
L L
V V
ArgDir ArgNeg s
I
× + ×
- < <
EQUATION1553 V2 EN (Equation 97)
where:
AngDir is the setting for the lower boundary of the forward directional characteristic, by default set to
15 (= -15 degrees) and
AngNegRes is the setting for the upper boundary of the forward directional characteristic, by default set
to 115 degrees, see figure 59.
V1
A
is positive sequence phase voltage in phase A
V1
AM
is positive sequence memorized phase voltage in phase A
I
A
is phase current in phase A
V1
AB
is voltage difference between phase A and B (B lagging A)
V1
ABM
is memorized voltage difference between phase A and B (B lagging A)
I
AB
is current difference between phase A and B (B lagging A)
The setting of AngDir and AngNegRes is by default set to 15 (= -15) and 115 degrees
respectively (as shown in figure 59). It should not be changed unless system studies
have shown the necessity.
ZDRDIR gives binary coded directional information per measuring loop on the output
STDIRCND.
STDIR=
FWD_A*1+FWD_B*2+FWD_C*4+FWD_AB*8+
+FWD_BC*16+FWD_CA*32+REV_A*64+REV_B*128+REV_C*256+
+REV_AB*512+REV_BC*1024+REV_CA*2048
1MRK504116-UUS C Section 3
IED application
185
Application manual

Table of Contents

Other manuals for ABB RET670

Related product manuals