EQUATION1899 V1 EN (Equation 125)
Reduced costs of power transmission due to decreased investment costs for
new power line
As shown in figure
77 the line loading can easily be increased 1.5-2 times by series
compensation. Thus, the required number of transmission lines needed for a certain
power transfer can be significantly reduced. The cost of series compensation is small
compared to the cost of a transmission line. When evaluating the cost of a transmission
system upgrade also the cost of secondary equipment such as eventual upgrading of
line protections on the compensated as well as, adjacent lines should be considered.
The main advantages of series compensation against the new transmission line within
the same corridor are:
• Significantly reduced investment costs; the same increase in power transmission
for up to 90% reduced costs
• In many cases, the only practical way to increase the transmission capacity of a
corridor
• Series compensation shortens the lead times
• Environmental impact
~
E
A ~
E
B
New transmission line
Series compensation
en06000594.vsd
IEC06000594 V1 EN
Figure 79: Series compensation is an important alternative to new transmission
lines
Advancements in series compensation using thyristor switching technology
A thyristor switched series capacitor (TSSC) can be used for power flow control. This
is performed by changing the reactance of the transmission circuit in discrete steps, as
shown in figure
80. A TSSC typically consists of a few segments in series that can be
inserted independently of each other in order to achieve different total series capacitor
reactance.
Section 3 1MRK504116-UUS C
IED application
210
Application manual