Name Values (Range) Unit Step Default Description
Characterist4 ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
- - ANSI Def. Time Selection of time delay curve type for step 4
Pickup4 1 - 2500 %IB 1 175 Phase current operate level for step4 in % of
IBase
t4 0.000 - 60.000 s 0.001 2.000 Definitive time delay of step 4
TD4 0.05 - 999.00 - 0.01 0.05 Time multiplier for the inverse time delay for
step 4
IMin4 1 - 10000 %IB 1 17 Minimum operate current for step4 in % of
IBase
t4Min 0.000 - 60.000 s 0.001 0.000 Minimum operate time for inverse curves for
step 4
MultPU4 1.0 - 10.0 - 0.1 2.0 Multiplier for current operate level for step 4
Table 90: OC4PTOC (51_67) Group settings (advanced)
Name
Values (Range) Unit Step Default Description
PUMinOpPhSel 1 - 100 %IB 1 7 Minimum current for phase selection in % of
IBase
2ndHarmStab 5 - 100 %IB 1 20 Pickup of second harm restraint in % of
Fundamental
ResetTypeCrv1 Instantaneous
IEC Reset
ANSI reset
- - Instantaneous Selection of reset curve type for step 1
tReset1 0.000 - 60.000 s 0.001 0.020 Reset time delay used in IEC Definite Time
curve step 1
tPCrv1 0.005 - 3.000 - 0.001 1.000 Parameter P for customer programmable
curve for step 1
tACrv1 0.005 - 200.000 - 0.001 13.500 Parameter A for customer programmable
curve for step 1
tBCrv1 0.00 - 20.00 - 0.01 0.00 Parameter B for customer programmable
curve for step 1
Table continues on next page
Section 3 1MRK504116-UUS C
IED application
416
Application manual