Set value
Mode
Formula used for complex power calculation
AB
EQUATION2058-ANSI V1 EN (Equation 374)
BC
EQUATION2059-ANSI V1 EN (Equation 375)
CA
EQUATION2060-ANSI V1 EN (Equation 376)
A
EQUATION2061-ANSI V1 EN (Equation 377)
B
EQUATION2062-ANSI V1 EN (Equation 378)
C
EQUATION2063-ANSI V1 EN (Equation 379)
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is smaller than the set pick up power value Power1(2)
Section 3 1MRK504116-UUS C
IED application
480
Application manual