Set value
Mode
Formula used for complex power calculation
A,B
EQUATION2041 V1 EN (Equation 387)
B,C
EQUATION2042 V1 EN (Equation 388)
C,A
EQUATION2043 V1 EN (Equation 389)
A
EQUATION2044 V1 EN (Equation 390)
B
EQUATION2045 V1 EN (Equation 391)
C
EQUATION2046 V1 EN (Equation 392)
The function has two stages that can be set independently.
With the parameter OpMode1(2) the function can be set Enabled/Disabled.
The function gives trip if the power component in the direction defined by the setting
Angle1(2) is larger than the set pick up power value Power1(2)
Section 3 1MRK504116-UUS C
IED application
488
Application manual