Figure 12: Delta DAC connected three-phase CT set
In this case, everything is done in a similar way as in the above described example,
except that for all used current inputs on the TRM the following setting parameters
shall be entered:
CT
prim
=800A
CT
sec
=1A
CTWyePoint=ToObject
ConnectionType=Ph-Ph
It is important to notice the references in SMAI. As inputs at Ph-Ph are expected to be
A-B, B-Crespectively C-A we need to tilt 180º by setting ToObject.
Example how to connect single-phase CT to the IED
Figure
13 gives an example how to connect the single-phase CT to the IED. It gives an
overview of the required actions by the user in order to make this measurement
available to the built-in protection and control functions within the IED as well.