Name Values (Range) Unit Step Default Description
tSynchronizing 0.00 - 600.00 s 0.01 0.00 Supervision time to get the signal
synchronizing in progress
tExecutionFB 0.00 - 600.00 s 0.01 30.00 Maximum time from command execution to
termination
tPoleDiscord 0.000 - 60.000 s 0.001 2.000 Allowed time to have discrepancy between
the poles
Table 152: SXCBR Non group settings (basic)
Name Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 0.100 Supervision time for the apparatus to move
after a command
tIntermediate 0.000 - 60.000 s 0.001 0.150 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end
position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SuppressMidPos Disabled
Enabled
- - Enabled Mid-position is suppressed during the time
tIntermediate
Table 153: SXSWI Non group settings (basic)
Name
Values (Range) Unit Step Default Description
tStartMove 0.000 - 60.000 s 0.001 3.000 Supervision time for the apparatus to move
after a command
tIntermediate 0.000 - 60.000 s 0.001 15.000 Allowed time for intermediate position
AdaptivePulse Not adaptive
Adaptive
- - Not adaptive Output resets when a new correct end
position is reached
tOpenPulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for open command
tClosePulse 0.000 - 60.000 s 0.001 0.200 Output pulse length for close command
SwitchType Load Break
Disconnector
Grounding Switch
HS Groundg.
Switch
- - Disconnector 1=LoadBreak,2=Disconnector,3=EarthSw,
4=HighSpeedEarthSw
SuppressMidPos Disabled
Enabled
- - Enabled Mid-position is suppressed during the time
tIntermediate
Section 3 1MRK504116-UUS C
IED application
614
Application manual