The signals from other bays connected to the module ABC_LINE (3) are described below.
Signals from bypass busbar
To derive the signals:
Signal
BB7_D_OP All line disconnectors on bypass WA7 except in the own bay are open.
VP_BB7_D The switch status of disconnectors on bypass busbar WA7 are valid.
EXDU_BPB No transmission error from any bay containing disconnectors on bypass busbar WA7
These signals from each line bay (ABC_LINE, 3) except that of the own bay are needed:
Signal
789OPTR 789 is open
VP789TR The switch status for 789 is valid.
EXDU_BPB No transmission error from the bay that contains the above information.
For bay n, these conditions are valid:
AND
BB7_D_OP
VP_BB7_D
EXDU_BPB
en04000477_ansi.vsd
AND
AND
789OPTR (bay 1)
789OPTR (bay 2)
. . .
. . .
789OPTR (bay n-1)
VP789TR (bay 1)
VP789TR (bay 2)
. . .
. . .
VP789TR (bay n-1)
EXDU_BPB (bay 1)
EXDU_BPB (bay 2)
. . .
. . .
EXDU_BPB (bay n-1)
ANSI04000477 V1 EN
Figure 239: Signals from bypass busbar in line bay n
Section 3 1MRK504116-UUS C
IED application
618
Application manual

Table of Contents

Other manuals for ABB RET670

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ABB RET670 and is the answer not in the manual?

ABB RET670 Specifications

General IconGeneral
Rated Frequency50/60 Hz
InputsAnalog and binary inputs
ApplicationProtection of power systems
Communication ProtocolsIEC 61850, DNP3, Modbus
Operating Temperature Range-25°C to +55°C
MountingRack mounted
Number of Binary InputsUp to 48
Number of Binary Outputs32
Protection FunctionsOvercurrent Protection
OutputsBinary outputs
EnclosureIP 54
TypeLine Differential Protection
Number of Analog Inputs24

Related product manuals