Name Values (Range) Unit Step Default Description
tVTmismatch 1 - 600 s 1 10 Time delay for VT supervision alarm
T1RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer1
T2RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer2
T3RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer3
T4RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer4
T5RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer5
T6RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer6
T7RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer7
T8RXOP Disabled
Enabled
- - Disabled Receive block operation from parallel
transformer8
TapPosOffs -5 - 5 - 1 0 Tap position offset in relation to the master
MFPosDiffLim 1 - 20 - 1 1 Limit for tap pos difference from master
tMFPosDiff 0 - 6000 s 1 60 Time for tap pos difference from master
Table 168: TR8ATCC (90) Non group settings (basic)
Name
Values (Range) Unit Step Default Description
TrfId T1
T2
T3
T4
T5
T6
T7
T8
- - T1 Identity of transformer
TRFNAME 0 - 13 - 1 NAME#-15 User define string for OUT signal 15
Xr2 0.1 - 200.0 ohm 0.1 0.5 Transformer reactance in primary ohms on
ATCC side
tAutoMSF 0 - 60 s 1 10 Time delay for command for auto follower
OperationAdapt Disabled
Enabled
- - Disabled Enable adapt mode
MFMode Follow Cmd
Follow Tap
- - Follow Cmd Select follow tap or follow command
CircCurrBk Alarm
Auto Block
Auto&Man Block
- - Alarm Alarm, auto block or auto&man block for high
circ current
Table continues on next page
1MRK504116-UUS C Section 3
IED application
703
Application manual