Name Values (Range) Unit Step Default Description
Obj22DefVar 1:BinCnt32EvWout
T
2:BinCnt16EvWout
T
5:BinCnt32EvWith
T
6:BinCnt16EvWith
T
- - 1:BinCnt32EvWou
tT
Object 22, default variation
Obj30DefVar 1:AI32Int
2:AI16Int
3:AI32IntWithoutF
4:AI16IntWithoutF
5:AI32FltWithF
6:AI64FltWithF
- - 3:AI32IntWithoutF Object 30, default variation
Obj32DefVar 1:AI32IntEvWoutF
2:AI16IntEvWoutF
3:AI32IntEvWithFT
4:AI16IntEvWithFT
5:AI32FltEvWithF
6:AI64FltEvWithF
7:AI32FltEvWithFT
8:AI64FltEvWithFT
- - 1:AI32IntEvWoutF Object 32, default variation
Table 188: MSTRS485 Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
ValMasterAddr No
Yes
- - Yes Validate source (master) address
AddrQueryEnbl No
Yes
- - Yes Address query enable
tApplConfTout 0.00 - 300.00 s 0.01 10.00 Application layer confim timeout
ApplMultFrgRes No
Yes
- - Yes Enable application for multiple fragment
response
ConfMultFrag No
Yes
- - Yes Confirm each multiple fragment
UREnable No
Yes
- - Yes Unsolicited response enabled
URSendOnline No
Yes
- - No Unsolicited response sends when on-line
UREvClassMask Disabled
Class 1
Class 2
Class 1 and 2
Class 3
Class 1 and 3
Class 2 and 3
Class 1, 2 and 3
- - Disabled Unsolicited response, event class mask
UROfflineRetry 0 - 10 - 1 5 Unsolicited response retries before off-line
retry mode
Table continues on next page