100305
IMagComp5
IMagComp30
IMagComp100
-10
+10
Magnitude
compensation
% of In
Measured
current
% of In
0-5%: Constant
5-30-100%: Linear
>100%: Constant
100305
IAngComp5
IAngComp30
IAngComp100
-10
+10
Angle
compensation
Degrees
Measured
current
% of In
ANSI05000652_3_en.vsd
ANSI05000652 V3 EN
Figure 305: Calibration curves
Setting examples
Three setting examples, in connection to Measurement function (CVMMXN), are
provided:
Measurement function (CVMMXN) application for a 400 kV OHL
Measurement function (CVMMXN) application on the secondary side of a
transformer
Measurement function (CVMMXN) application for a generator
For each of them detail explanation and final list of selected setting parameters values
will be provided.
The available measured values of an IED are depending on the actual
hardware (TRM) and the logic configuration made in PCM600.
Section 3 1MRK504116-UUS C
IED application
754
Application manual