Table 217: CMMXU Non group settings (basic)
Name Values (Range) Unit Step Default Description
IA_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Operation Disabled
Enabled
- - Disabled Disbled/Enabled operation
IBase 1 - 99999 A 1 3000 Base setting for current level in A
IA_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IA_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IA_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IB_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IB_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IB_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_DbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
IC_Max 0.000 -
10000000000.000
A 0.001 1000.000 Maximum value
IC_RepTyp Cyclic
Dead band
Int deadband
- - Cyclic Reporting type
IC_AngDbRepInt 1 - 300 Type 1 10 Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
Table 218: CMMXU Non group settings (advanced)
Name
Values (Range) Unit Step Default Description
IA_ZeroDb 0 - 100000 m% 1 0 Zero point clamping in 0.001% of range
IA_HiHiLim 0.000 -
10000000000.000
A 0.001 900.000 High High limit (physical value)
IA_HiLim 0.000 -
10000000000.000
A 0.001 800.000 High limit (physical value)
IMagComp5 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 5% of
In
IMagComp30 -10.000 - 10.000 % 0.001 0.000 Magnitude factor to calibrate current at 30%
of In
Table continues on next page
1MRK504116-UUS C Section 3
IED application
765
Application manual