TimeSynch
When the source of the time synchronization is selected on the local HMI, the
parameter is called TimeSynch. The time synchronization source can also be set from
PCM600. The setting alternatives are:
FineSyncSource which can have the following values:
Disabled
SPA
LON
BIN (Binary Minute Pulse)
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
GPS+IRIG-B
IRIG-B
PPS
CoarseSyncSrc which can have the following values:
Disabled
SPA
LON
SNTP
DNP
CoarseSyncSrc which can have the following values:
SNTP
DNP
IEC60870-5-103
The function input to be used for minute-pulse synchronization is called TIME-
MINSYNC.
The system time can be set manually, either via the local HMI or via any of the
communication ports. The time synchronization fine tunes the clock (seconds and
milliseconds).
Section 3 1MRK504116-UUS C
IED application
76
Application manual