EasyManua.ls Logo

ABB RET670 - Page 84

ABB RET670
888 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Table 9: TIMESYNCHGEN Non group settings (basic)
Name Values (Range) Unit Step Default Description
CoarseSyncSrc Disabled
SPA
LON
SNTP
DNP
- - Disabled Coarse time synchronization source
FineSyncSource Disabled
SPA
LON
BIN
GPS
GPS+SPA
GPS+LON
GPS+BIN
SNTP
GPS+SNTP
IRIG-B
GPS+IRIG-B
PPS
- - Disabled Fine time synchronization source
SyncMaster Disabled
SNTP-Server
- - Disabled Activate IED as synchronization master
TimeAdjustRate Slow
Fast
- - Fast Adjust rate for time synchronization
HWSyncSrc Disabled
GPS
IRIG-B
PPS
- - Disabled Hardware time synchronization source
AppSynch NoSynch
Synch
- - NoSynch Time synchronization mode for application
SyncAccLevel Class T5 (1us)
Class T4 (4us)
Unspecified
- - Unspecified Wanted time synchronization accuracy
Table 10: SYNCHBIN Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ModulePosition 3 - 16 - 1 3 Hardware position of IO module for time
synchronization
BinaryInput 1 - 16 - 1 1 Binary input number for time synchronization
BinDetection PositiveEdge
NegativeEdge
- - PositiveEdge Positive or negative edge detection
Table 11: SYNCHSNTP Non group settings (basic)
Name
Values (Range) Unit Step Default Description
ServerIP-Add 0 - 18 IP
Address
1 0.0.0.0 Server IP-address
RedServIP-Add 0 - 18 IP
Address
1 0.0.0.0 Redundant server IP-address
Section 3 1MRK504116-UUS C
IED application
78
Application manual

Table of Contents

Other manuals for ABB RET670