EasyManua.ls Logo

ACO 6236 - Detail of Command

ACO 6236
154 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
58
Detail of Command
Normal CommandNormal Sound Level Meter MODE
CMD
Function Item
Data Item
Function Outline
T
Time and data
setting request
ASCII(13)
YYMMDDHHMMSS
t
Time and data
setting completed
Data division note
F Transfer
configuration file
ASCII(5) A B C D E
A Meas.Time select1
0*** 11s 23s
35s 410s 51m
65m 710m 815m
930m A1h
B8h
C12h D24h
B Range setting1
0130dB 1120dB
2110dB 3100dB
490dB 580dB
C Filter setting1
0A 1C 2Z
D Time constant1
0FAST 1Slow 2Imp
E Interval1
0 single 1repeat
f
Data division none
I
Set
confirmation
command
Data division none
Set forwarding
ASCII(5) Conforming of configuration file
S Start measurement
Data division none
s Start measurement
E Stop measurement
Data division none
e
r Data acquisition
Data division none
D
Data request
Data division none
Data transfer
ASCII()
C CAL
Data division none
Operation
CAL (It stop again by C or E)
L
Data request
Data division none
Operation
It turns it off by E
R
Range
single specification
ASCII(1)
0130 1120・・・・・580
Operation
Data division none
A Filter specification
ASCII(1)
0A 1C 2F
Operation
Data division none
P
Lp-value
acquisition
Data division none
Data transfer ASCII(5)
M L
atm5
start Data division none
m Data acquisition after “r” command is received
Q L
Aleq
start Data division none
q Measurement start Data acquisition after “r” command is received

Table of Contents