61179641L4-5B 1-5
CAUTION
Per GR-1089-CORE the Total Access 1248 is designed and
intended for installation as part of a Common Bonding Network
(CBN). The Total Access 1248 is not designed nor intended for
installation as part of an Isolated Bonding Network (IBN).
CAUTION
Per GR-1089-CORE Section 9, the Total Access 1248 is intended to
be deployed in either a DC-C (common) or DC-I (isolated) installa-
tion of the Total Access 1248.
CAUTION
The Total Access 1248 Chassis frame ground terminal must be
connected to a reliable earth ground.
CAUTION
Connect to a reliably grounded –48 VDC source which is electri-
cally isolated from the AC source. The branch circuit overcurrent
protection shall be a fuse or circuit breaker rated minimum
48 VDC, maximum 3 amp.
NOTE
The
POTS and ADSL+POTS ports are classified as Type 1, 3, and 5
as defined in Appendix B of GR-1089-CORE, Issue 4 and meets the
lightning and power fault criteria with any primary protector that
meets any of the voltage limits of GR-974-CORE or GR-1361-CORE
(i.e., carbon blocks, gas tubes, solid states, etc.). Solid-state
primary protectors are not recommended as they could affect the
signal integrity of the ADSL.
NOTE
Current limiting protectors are not required.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the ADTRAN Total Access 1248 and is the answer not in the manual?

ADTRAN Total Access 1248 Specifications

General IconGeneral
BrandADTRAN
ModelTotal Access 1248
CategoryNetwork Router
LanguageEnglish

Related product manuals