© Agilent Technologies 1989–2002 Agilent 3070 / 79000 Site Preparation 10-84
Chapter 10: Site Preparation – Power Requirements for Older Systems: Series 3 Power Requirements and Connections (Prior to May 2000)
Table 10-8 Series 3 and 79000 family power requirements (3-phase power)
E1135C
Power
Option Voltage Full-Load Amps (FLA)
1
for:
2
327X / 79000
3
317X 307X 3-phase
xDSL/POTS
Bay
1- phase
xDSL/POTS
Bay
4
Opts/Current
Testhead Support Bay
3-Phase Wye w/ Neutral AWW 120 /
208
[15]
5
14 [23] 18 [42] 28 NA 12 AWV, 16
05E 127 /
220
[15] 14 [23] 18 [42] 28 NA 12 AWZ, 16
0E5 220 /
380
[13] 10 [14] 10 [22] 18 NA 10 05M, 14
05L 230 /
400
[13] 10 [14] 10 [22] 18 NA 10 05F, 14
0E7 240 /
415
[13] 10 [14] 10 [22] 18 NA 10 05J, 14
3-phase Delta 0ED 200 [15] 14 [23] 18 [42] 28 NA 12 AWY, 16
05C 220 [15] 14 [23] 18 [42] 28 NA 12 0E3, 16
05H 230 [15] 14 [23] 18 [42] 28 NA 12 03G, 16
0E6 240 [15] 14 [23] 18 [42] 28 NA 12 0EH, 16
L1
L
L2
N
G
L1
L3 L2
G