© Agilent Technologies 1989–2002 Agilent 3070 / 79000 Site Preparation 10-119
Chapter 10: Site Preparation – Power Requirements for Older Systems: Tester Power Requirements (Series I/II)
Table 10-23 E1099A option 0EC mains requirements
Device Current (Amps) 240 Volts Single-Phase
Module 1 9.6
Module 2 9.6
Module 3 9.6
Module 4 9.6
+5 V STC P.S. #1 2.9
+5 V STC P.S. #2 2.9
+5 V STC P.S. #3 2.9
+5 V STC P.S. #4 2.9
DUT Power #1 3.0
DUT Power #2 3.0
DUT Power #3 3.0
DUT Power #4 3.0
Aux. Equipment 2.0
Controller/Peripherals 20.0
* Total current: