EasyManua.ls Logo

Allen-Bradley Kinetix 300 - Power Wiring Examples

Allen-Bradley Kinetix 300
230 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Rockwell Automation Publication 2097-UM001D-EN-P - November 2012 173
Interconnect Diagrams Appendix A
Power Wiring Examples
You must supply input power components. The single-phase and three-phase line
filters are wired downstream of fusing and the M1 contactor.
In this example, the 2097-V31PRx drives are wired to use the voltage doubling
circuit. The 120V input voltage provides 240V output to motors. The 2097-
V33PRx drives are wired for single-phase 120V operation.
Figure 83 - Kinetix 300 Drive (120V single-phase input power)
PE
N
L1
+24V DC
+
+
SH
-
-
EN
ACOM
RDY +
RDY -
L1
L2/N
29
26
41
42
U
V
W
PE
L2/N
PE
L2
L3
L1
2097-V31PRx
2097-V33PRx
Return
Single-phase AC Input
120V rms AC, 50/60 Hz
Notes 1, 2
Bonded Cabinet
Ground Bus *
Ground Stud
Mains
Single-phase
AC Input
(IPD) Connector
Fuse Disconnect
or Circuit Breakers
Input Fusing * M1 *
Notes 5, 7
Use discrete logic or PLC
to control ENABLE to drive
and monitor RDY signal
back from drive.
Shunt Resistor
and DC Bus
(BC) Connector
Motor Power
(MP) Connector
I/O (IOD)
Connector
Back-up Power
(BP) Connector
2097-V31PRx and 2097-V33PRx
Kinetix 300 Drives
* Indicates User Supplied Component
See table on page 172 for note information.
AC Line Filter
(Optional)
Note 3
Three-phase
Motor Power
Connections
Note 9
Cable Shield
Clamp
Note 8
Shunt Resistor
Connections
User-supplied
+24V DC

Table of Contents

Related product manuals