EasyManuals Logo

Allen-Bradley Stratix 5700 User Manual

Allen-Bradley Stratix 5700
548 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #131 background imageLoading...
Page #131 background image
Rockwell Automation Publication 1783-UM007G-EN-P - February 2017 131
Install Stratix 5700 Switches Chapter 5
Temperature surrounding the unit does not exceed 60 °C (140 °F).
Clearance to front and rear panels meets these conditions:
Front-panel status indicators can be easily read.
Access to ports is sufficient for unrestricted cabling.
Front-panel direct current (DC) power connectors and the alarm
relay connector are within reach of the connection to the DC power
source.
Cabling is away from sources of electrical noise, such as radios, power
lines, and fluorescent lighting fixtures.
Connect the unit to only a Class 2 DC power source.
Follow these steps to install the switch.
1. (Optional) Install or remove the SD card.
2. Verify switch operation.
3. Mount the switch on a DIN rail.
4. Ground the switch.
5. Wire the DC power source for the switch and attach the switch power
connectors.
6. (Optional) Wire the Power over Ethernet (PoE) DC power source and
attach the PoE power connector.
7. (Optional) Install an SFP module.
8. Wire external alarms and attach the alarm relay connector to the switch.
9. Connect to the switch ports:
10/100 copper ports and 10/100/1000 ports
10BASE-T, 100BASE-TX, and 10000BASE-T ports
•PoE ports
SFP module ports
Dual-purpose ports
IMPORTANT When the switch is installed in an industrial enclosure, the
temperature within the enclosure is greater than normal room
temperature outside the enclosure.
The temperature inside the enclosure cannot exceed 140 °F (60 °C),
the maximum ambient enclosure temperature of the switch.
ATTENTION: Do not wire more than 1 conductor on any single terminal.

Table of Contents

Other manuals for Allen-Bradley Stratix 5700

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Allen-Bradley Stratix 5700 and is the answer not in the manual?

Allen-Bradley Stratix 5700 Specifications

General IconGeneral
ModelStratix 5700
Port TypesRJ45, SFP
MountingDIN Rail or Panel Mount
DimensionsVaries by model
WeightVaries by model
ManagementWeb-based, SNMP, Command Line
RedundancyDevice Level Ring, STP, RSTP
Operating Temperature-40°C to 70°C
Power SupplyDual DC inputs
Input Voltage24 VDC or 100-240 VAC
ProtocolsEtherNet/IP, DLR
Security FeaturesSSH, HTTPS, RADIUS, TACACS+