4. Configuration
54
FLAG_INACCURATE
ANY
-
FLAG_OLD_DATA
ANY
NOT TOPICAL
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
BLOCKED
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Table 4-10. Digital Points Conversion Internal to IEC 60870-5-104
Internal -> IEC 60870-5-104 Analog
Internal Quality
IEC 60870-5-104 Quality
Flags
VALIDITY
FLAG_RESTART
ANY
NOT TOPICAL
FLAG_COMM_FAIL
ANY
NOT TOPICAL
FLAG_REMOTE_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_LOCAL_SUBSTITUTED
ANY
SUBSTITUTED
FLAG_FILTER
ANY
-
FLAG_OVERFLOW
ANY
OVERFLOW
FLAG_REFERENCE_ERROR
ANY
INVALID
FLAG_INCONSISTENT
ANY
INVALID
FLAG_OUT_OF_RANGE
ANY
OVERFLOW
FLAG_INACCURATE
ANY
INVALID
FLAG_OLD_DATA
ANY
NOT TOPICAL
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
BLOCKED
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Table 4-11. Analog Points Conversion Internal to IEC 60870-5-104
Internal -> IEC 60870-5-104 Counters
Internal Quality
IEC 60870-5-104 Quality
Flags
VALIDITY
FLAG_RESTART
ANY
-
FLAG_COMM_FAIL
ANY
-
FLAG_REMOTE_SUBSTITUTED
ANY
-
FLAG_LOCAL_SUBSTITUTED
ANY
-
FLAG_FILTER
ANY
-
FLAG_OVERFLOW
ANY
OVERFLOW
FLAG_REFERENCE_ERROR
ANY
-
FLAG_INCONSISTENT
ANY
-
FLAG_OUT_OF_RANGE
ANY
-
FLAG_INACCURATE
ANY
-
FLAG_OLD_DATA
ANY
-
FLAG_FAILURE
ANY
INVALID
FLAG_OPERATOR_BLOCKED
ANY
-
FLAG_TEST
ANY
-
ANY
VALIDITY_INVALID
INVALID
Table 4-12. Counters Conversion Internal to IEC 60870-5-104