Annex A. DNP3 Interoperability
380
DNP V3.0 Implementation Table
DNP OBJECT GROUP & VARIATION
REQUEST
Master may issue
Outstation must parse
RESPONSE
Master must parse
Outstation may issue
Group
Num
Var
Num
Description
Function
Codes
(dec)
Qualifier
Codes
(hex)
Function
Codes
(dec)
Qualifier
Codes
(hex)
1
0
Binary Input – Any
Variation
1 (read)
00, 01 (start-
stop)
06 (no range,
or all)
1
1
Binary Input – Packed
format
1 (read)
00, 01 (start-
stop)
06 (no range,
or all)
129
(response)
00, 01
(start-stop)
2
0
Binary Input Event – Any
Variation
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
2
2
Binary Input Event – With
absolute time
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
129
(response)
17, 28
(index)
60
1
Class Objects – Class 0
data
1 (read)
06 (no range,
or all)
60
2
Class Objects – Class 1
data
1 (read)
06 (no range,
or all)
07, 08 (limited
qty)
80
1
Internal Indications –
Packed format
1 (read)
00, 01 (start-
stop)
129
(response)
00 (start-
stop)
2 (write)
00 (start-stop)
index=7