2. Technical Description
9
Conformal coating
Yes
IP Level
IP 20
Standards
IEC 61131-2
IEC 61131-3
CE, Electromagnetic Compatibility (EMC) and Low-Voltage
Directive (LVD).
Module dimensions (W x H x D)
36.00 x 114.63 x 115.30 mm
Package dimensions (W x H x D)
44.00 x 122.00 x 147.00 mm
Weight
350 g
Weight with package
400 g
Table 2-4. Common Features
Notes:
Tasks: Task is an object used to call POUs. A Task can be triggered by period, events or can run in
freewheeling mode. Each task can call one or more POUs.
Real Time Clock (RTC): The retention time, time that the real time clock will continue to update
the date and time after a CPU power down, is 15 days for operation at 25 ºC. At the maximum
product temperature, the retention time is reduced to 10 days.
Isolation: The term logic is used to refer to the internal circuits such as processor, memory and bus
interfaces.
Conformal coating: The covering of electronic circuits protects internal parts of the product against
moisture, dust and other harsh elements to electronic circuits.
Specific Features
NX3004
NX3005
NX3010
NX3020
NX3030
Addressable input variables memory (%I)
32 Kbytes
32 Kbytes
32 Kbytes
64 Kbytes
96 Kbytes
Addressable output variables memory (%Q)
32 Kbytes
32 Kbytes
32 Kbytes
64 Kbytes
96 Kbytes
Addressable variables memory (%M)
16 Kbytes
16 Kbytes
16 Kbytes
32 Kbytes
64 Kbytes
Symbolic variables memory
2 Mbytes
3 Mbytes
4 Mbytes
5 Mbytes
6 Mbytes
Maximum amount of memory configurable as
retentive or persistent
7.5 Kbytes
7,5 Kbytes
64 Kbytes
112 Kbytes
112 Kbytes
Total redundant data memory
-
-
-
-
736 Kbytes
Addressable input variables memory (%I)
-
-
-
-
80 Kbytes
Addressable output variables memory (%Q)
-
-
-
-
80 Kbytes
Addressable variables memory (%M)
-
-
-
-
64 Kbytes
Symbolic variables memory
-
-
-
-
512 Kbytes
Program memory
3 Mbytes
3 Mbytes
4 Mbytes
6 Mbytes
8 Mbytes
Source code memory (backup)
32 Mbytes
40 Mbytes
40 Mbytes
80 Mbytes
120 Mbytes
User files memory
16 Mbytes
16 Mbytes
16 Mbytes
32 Mbytes
32 Mbytes
Maximum number of tasks
16
16
16
24
32
Maximum number of expansion bus
1
4
8
24
24
Maximum number of I/O modules on the bus
32
64
128
128
128
Ethernet TCP/IP local interface
1
1
1
2
2
Maximum number of additional Ethernet TCP/IP
interface modules
0
1
0
2
6
Ethernet TCP/IP interface redundancy support
No
No
No
Yes
Yes