Page 209 of 308
3. Press the SELECT key to display the routing configuration menu.
sue: 03 complete, approved
14.2.6 Routing Contact DVA Play Mode Configuration
This setting is only relevant when a ‘Routing’ contact is used for control of DVA routes.
The DVAs assigned to a contact may be configured to cease playing immediately that the route is terminated
(DVA-Part), or play until the end of the message and then stop (DVA-Full).
In order to set the DVA play mode proceed as follows.
1. Select ConfigurationÆSystemÆRouterÆControlÆContacts.
2. Move to, and scroll the contact list until the required contact is displayed in the left field:
[Contact#nn] Routing Not-Surv
Default value: ‘Contact#01’
Contact numbers: 01 to 22 for VAR4
01 to 42 for VAR12
01 to 62 for VAR20
Where contacts: 00 to 10 are analogue
11 to 62 are opto-isolated
4. Move to, and select the Control menu item:
Zoning [Control] Clear-all
5. Move to, and toggle to the required play mode in the right field:
Latching Busy=On [DVA-Full]
• [DVA-Full]
The repeating DVA broadcast will play to the end of the message before stopping when the trigger
is de-asserted.
• [DVA-Part]
The repeating DVA broadcast will stop immediately when the trigger is de-asserted.
Default value: ‘DVA-Full’
Note: If the Routing contact is configured to Play Once, this setting should be DVA-Full.
6. Save the changes by pressing the SELECT key, or cancel by pressing the BACK key.