VAR4 / VAR12 / VAR20 - Operation Manual
Is
Page 300 of 308
sue: 03 complete, approved
Setting Default Value
Output
Output name OUTPUT nn
nn=output number
Output level
10dB
EQ Enabled / 0dB all bands
Surveillance mode Pulsed
Surveillance tone level
12dB
Override gain
30dB
Output ANS Off
Number of Induction Loop Outputs 0
PTT button
PTT button (zoned fire and paging microphones) All Call Disabled / Restore Disabled
PTT button cough timeout 0 (10th Sec)
DVA
DVA modes DVA Full
Busy indication On
Contact
Contact Not-Conf
External fault description EXT FAULT
Music
Music Fixed A
Mainframes / Amplifiers
Mainframe description Blank
Report over-temperature No
Maximum temperature 70°C
Amplifier description Blank
Amplifier AC surveillance No
Amplifier AC surveillance input and output thresholds 0000mV
Amplifier AC surveillance interval 00
Amplifier DC surveillance No
Amplifier Earth Leakage monitoring No
Remote Units (RS485 bus)
Bus address Not Configured
Noise Reduction
Night time volume control Off
Night time volume control active time SUN Sta: 22:00 Dur: 10:00
MON Sta: 23:00 Dur: 9:00
TUE Sta: 23:00 Dur: 9:00
WED Sta: 23:00 Dur: 9:00
THU Sta: 23:00 Dur: 9:00
FRI Sta: 23:00 Dur: 9:00
SAT Sta: 23:00 Dur: 11:00
Max output level during night time volume control time 0dB