6-13
Auto-tuning always calculates the excess time and limit sensitivity of thread for
two limit cycles and calculates PID values using characteristics equations, then
automatically writes the results.
The setup data C21 setting changes the upper and lower output limit used
during auto-tuning.
C21 setting of 1, 3 or 5 causes the lower output limit to be determined by
variable parameter PA09 and the upper output limit to be determined by PA10.
C21 setting of 2 or 4, lower output limit is off and the upper output limit is on.
The point at which output reverses (lower limit upper limit) during auto-
tuning is determined from the SP and PV values at AT startup as follows.
Auto-tuning performed using a variable parameter PA08 setting of 3 or 4
causes auto-tuning to be performed on SP, PID parameters tP-A1 to tP-A7, in
order.
Auto-tuning can be started by the AT key, external switch input and by
transmission. The AT LED flashes during auto-tuning.
Auto-tuning terminates without writing PID constants and the AT LED goes off
when any of the following conditions occur.
Operation is terminated by pressing of the AT key.
Operation is terminated by an external switch input.
Operation is terminated by transmission.
Mode change occurs. (When the MANUAL mode is invoked; the READY
mode is invoked by setting PA08 to 1 or 2, the RUN mode is invoked by
setting PA08 to 3 or 4.)
When PV goes outside the range.
Time
PV
tP-A7
tP-A6
tP-A5
tP-A4
tP-A3
tP-A2
tP-A1
SP
AT start Normal end
Time
When PV > SP
When PV < SP
Starting
2/3
2/3
1/3
1/3
SP
AT start Normal end
Time
Running SP = PV
PV PV
Chapter 6. OPERATION