2 - 3 Input Type and Range Number
2-8
■ Input
● Thermocouple
● Resistance temperature detector (RTD)
Chapter 2. NAMES AND FUNCTIONS OF PARTS
Input type
Symbol
Code
Accuracy (under standard conditions)
±0.1%FS
Input range (FS)
Range No.
K (CA) K46
-200.0 to +200.016
-300.0 to +400.0
±0.1%FSK (CA) K09
0.0 to 1200.000 to 2400
±0.1%FSK (CA) K08
0.0 to 800.010 to 1600
±0.1%FSK (CA) K04
0.0 to 400.020 to 750
±0.1%FSE (CRC) E08
0.0 to 800.030 to 1800
±0.1%FSJ (IC) J08
0.0 to 800.040 to 1600
±0.1%FST (CC) T44
-200.0 to +300.0
5 -300 to +700
±0.1%FSB (PR30-6) B18
0.0 to 1800.060 to 3300
±0.1%FSR (RR13) R16
0.0 to 1600.070 to 3100
±0.1%FSS (PR10) S16
0.0 to 1600.080 to 3100
±0.1%FSW (WRe5-26) W23
0.0 to 2300.090 to 4200
±0.1%FSW (WRe5-26) W14
0.0 to 1400.010 0 to 2552
±0.2%FSPR40-20 D19
0.0 to 1900.011 0 to 3400
±0.1%FSN U13
0.0 to 1300.012 32 to 2372
±0.1%FSPL II Y13
0.0 to 1300.013 32 to 2372
±0.1%FSZ13
0.0 to 1300.014 32 to 2372
±0.4%FS
Gold, iron, chromel
Z06
0.0 to 300.0K (K : Kelvin)15
Input type
Symbol
Code
Accuracy (under standard conditions)
±0.1%FS
Input range (FS)
Range No.
JIS’89Pt100 F50
-200.0 to +500.064 -
300.0 to +900.0
±0.1%FSF46
-200.0 to +200.065 -
300.0 to +400.0
±0.1%FSF32
-100.0 to +150.0
66 -
150.0 to +300.0
±0.1%FSF36
-50.0 to +200.067 -50.0 to +400.0
±0.15%FSF33
-40.0 to +60.068 -40.0 to +140.0
±0.15%FSF01
0.0 to 100.069 0.0 to 200.0
±0.1%FSF03
0.0 to 300.070 0.0 to 500.0
±0.1%FSF05
0.0 to 500.071 0.0 to 900.0
±0.1%FSJIS’89Pt100 P50
-200.0 to +500.096 -
300.0 to +900.0
±0.1%FSP46
-200.0 to +200.097
-300.0 to +400.0
±0.1%FSP32
-100.0 to +150.098
-150.0 to +300.0
±0.1%FSP36
-50.0 to +200.099 -50.0 to +400.0
±0.15%FSP33
-40.0 to +60.0100 -40.0 to +140.0
±0.15%FSP01
0.0 to 100.0101 0.0 to 200.0
±0.1%FSP03
0.0 to 300.0102 0.0 to 500.0
±0.1%FSP05
0.0 to 500.0103 0.0 to 900.0