8-7
Setting event items
Handling Precautions
Note that when setup data C57 is set to 1, event items on the programming
map are skipped and not displayed.
When the event is a PV event
(1) In the set value display state, move to the segement event item to be set on the
programming map.
(2) Press the ENTER key to make display panel 1 flash (registration of first
setting).
(3) Use the , , , and keys to make the first setting – setting the event
operating point.
Setting range : OFF –19999 to +20000 SPU
: OFF 0 to 20000 SPU (for absolute value deviation events)
: OFF –5.0 to +105.0% (for MV events)
(4) Press the ENTER key to stop the flashing on display panel 1. (Pressing the
FUNC and CLR keys causes display panel 1 to return to unset state “-----”
and the flashing stops.)
Display (PV events)
Unset values are indicated as “ ----- ”.
NOTE
A PV event setting consists of a setting (including OFF) and a subfunction. A
subfunction cannot be used when a setting has not been made “ ----- ”.
PROG SEG
PROFILE
Program
number
Segment
number
Set operating point
Pattern trend
Event number
Event type
Chapter 8. PROGRAM SETUP