4  -  5 Power Supply and Grounding
4-6
■ Power supply
To supply power to the DCP551, use an instrument-dedicated single-phase power
supply subject to minimal electrical interference.
Handling Precautions
• If electrical interference proves excessive, we recommend adding an
insulating transformer and/or using a line filter.
Azbil Corporation model no.: 81442557-001
• After carrying out interference reducing measures, do not bundle the
primary and secondary power supply coils together or insert them in the
same conduit or duct.
■ Grounding
If grounding the shield wire or other lines proves difficult, ground them separately
to a grounding terminal block.
Ground resistance : Less than 100Ω
Conductor : Annealed copper wire, min. 2mm
2
(AWG14)
Max. Length : 20m
Handling Precautions
To ground the DCP551, connect the FG terminal (terminal
(52) or (53) 
)
to a single ground point without jumpering.