■ SP output
When the programmer function is used (when setup data C21 is set to 0), SP
output is processed as shown below.
■ Auxiliary output
● Auxiliary output 1
Auxiliary output 1 is processed as shown below by a model with one or two
auxiliary output channels.
● Auxiliary output 2
Auxiliary output 2 is processed as shown below on a model with two auxiliary
output channels.
SP
Setup: programmer SP (in programmer operation mode) variable 
parameter 
PA11
Upper and lower limit scaling
Setting: setup data 
C52
, 
C53
Manipulated variable in READY mode
Setting: setup data 
C32
In READY AUTO mode
MANUAL SP
In MANUAL mode
Output 1
Current output 4 to 20mA
Auxiliary output 1 type
Setting: setup data 
C45
Upper and lower limit scaling
Setting: setup data 
C46
, 
C47
4mA
•  
When the auxiliary output type is SP 
or deviation in the READY mode.
•  
When the auxiliary output type is PV2 
and a model with a PV input channel 
is used.
Auxiliary output 1
Current output 4 to 20mA
Auxiliary output 2 type
Setting: setup data 
C48
Upper and lower limit scaling
Setting: setup data 
C49
, 
C50
4mA
•  
When the auxiliary output type is SP 
or deviation in the READY mode.
•  
When the auxiliary output type is PV2 
and a model with a PV input channel 
is used.
Auxiliary output 2
Current output 4 to 20mA