0: Program run mode
1: Constant value control mode
[Description:]
When setup 
C21
 is set to 0, this setting is automatically 
set to 0.
0
ConSt
1
Control mode
Within the range of setup 
C66
 to 
C67
 (SP limit)
0
SP
2
Setpoint
0.0  to 1000.0%
A setting of 0.0 turns on ON-OFF control
100.0
P
3
Proportional band
0 to 3600sec
No integral operation when set to 0.
[Description:]
When 
P
 is set to 0.0, “-----” is displayed and setting is not possible.
0
I
4
Integral time
0 to 1200 sec
No integral operation when set to 0.
[Description:]
When 
P
 is set to 0.0, “-----” is displayed and setting is not possible.
0
d
5
Derivative time
0.0  to 100.0%
[Description:]
When 
P
 is set to 0.0, “-----” is displayed and setting is not 
possible.When I is not equal to 0, “-----” is displayed and setting 
is not possible.
50.0
rE
6
Manual reset
-5.0% to upper limit 
0.0
oL
7
Manipulated variable lower limit
Lower limit to +105%
100.0
oH
8
Manipulated variable upper limit
Item code
Item
No.
User 
settings
Settings and descriptions
Factory default 