10-6
● General reset is not possible with FUNC, CLR and MESSAGE keys
■ Parameter setting related problems
● Registration state cannot be invoked with ENTER key
■ Program setting related problems
● Registration state cannot be invoked with ENTER key
● Item changes cannot be made with and keys
● SP values in program settings cannot be changed with and keys
● Event items cannot be displayed with and keys
Cause Measure
Event type is something other than segment
type.
Set the event type in the event configuration data to a value
between 1 and 23.
Programming item sets no display. Set setup data
C57
to 0.
Cause Measure
SP limit sets error value. Set correct value for setup data
C66
and
C67
.
Cause Measure
Not pattern item set. Set SP and time data.
Cause Measure
Set to memory protect. Set variable parameter
PA02
to 0, 2 or 4.
Cause Measure
“-----” displayed in display panel 2 This item cannot be displayed or set. To change setting
connection item, it may be able to change or set.
Data displayed in display panel 2 cannot be changed.
This item is display only.
Set to memory protect. Set variable parameter
PA02
to 0.
Cause Measure
Normal display mode not on Press DISP key to invoke normal display mode.
Mode other than READY mode Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Set to MANUAL mode. Set AUTO mode to execute AUTO operation (A/M key).
Set to memory protect. Set variable parameter
PA02
to 0.
Set to key lock. Set variable parameter
PA01
to 0.
Chapter 10. MAINTENANCE AND TROUBLESHOOTING