10-5
● Autotuning cannot be canceled with AT key
● PID parameter setting state cannot be invoked with PID key
● Event configuration setting state cannot be invoked with FUNC and PARA keys
● Setup data setting state cannot be invoked with SETUP key
● Constant value control data setting state cannot be invoked with FUNC and PID keys
● Program setting state cannot be invoked with FUNC and PROG keys
● Program copy is not possible with and PROG keys
Cause Measure
Set to be except READY mode. Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Program selected in READY mode is unset. Select number of a set program.
Constant value control mode is on. Set constant value control data
ConSt
to 0.
Mode other than READY Press DISP key to invoke normal display mode.
Program protected Set variable parameter
PA02
to 0, 2 or 4.
Set to key lock. Set variable parameter
PA01
to 0.
Cause Measure
Normal display mode not on Press DISP key to invoke normal display mode.
Set to constant value control mode. Set constant value control data
ConSt
setting to 0.
Set to key lock. Set variable parameter
PA01
between 0 to 2.
Cause Measure
Normal display mode not on Press DISP key to invoke normal display mode.
Mode other than READY Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Set to key lock. Set variable parameter
PA01
between 0 to 2.
Cause Measure
Normal display mode not on Press DISP key to invoke normal display mode.
Mode other than READY Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Set to key lock. Set variable parameter
PA01
between 0 to 2.
Cause Measure
Normal display mode not on Press DISP key to invoke normal display mode.
Set to key lock. Set variable parameter
PA01
to 0 or 2.
The programmer function is set. Set setup data
C21
to any value other than 0.
Cause Measure
Set to key lock. Set variable parameter
PA01
between 0 to 2.
Chapter 10. MAINTENANCE AND TROUBLESHOOTING