7-21
Setup data setting
0 to 16 : T/C
48 to 52 : linear (DC current, DC voltage)
64 to 71 : RTD
96 to 103 : RTD
128 to 134: linear (DC current, DC voltage)
[Description:]
For details see range numbers listed in “Section 2-3
Input Type and Range Number” (page 2-8)
0
C 01
1
PV1 range number
0
C
02
2
PV1 temperature unit
1
C
03
3
PV1 decimal point position
0 to 4
A setting of 0 means no decimal point and a setting
between 1 and 4 indicates the number of decimal digits.
[Description:]
C01 settings for t/c and RTD display “-----” and setting is
not possible.
When setting
C01
is linear, this setting is reflected in
PVU (PV1) units.
1
C
04
4
PV1 linear decimal point
position
-19999 to +20000 PVU (PV1)
[Description:]
C01
settings for t/c and RTD display “-----” and setting is
not possible.
Reversing the lower limit and upper limit makes it
possible to reverse analog inputs and specified values.
0 PVU
C
05
5
PV1 linear range lower limit
10000PVU
C
06
6
PV1 linear range upper limit
0: Provided (compensated internally)
1: Not provided (compensated externally)
[Description:]
C01
settings for T/C and RTD display “-----” and setting
is not possible.
0
C
07
7
PV1 cold junction
compensation
0: Not provided
1: Provided
[Description:]
C01
settings for t/c and RTD display “-----” and setting is
not possible.
0
C
08
8
PV1 square root extraction
0.2 to 10.0% (ratio depends on input range)
[Description:]
C01
settings for T/C and RTD display “-----” and setting
is not possible.
0.2
C
09
9
PV1 square root extraction
dropout
0.0
C
10
10
PV1 cold junction bias
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
0 to 2
A setting of 0 means no decimal point and a setting of 1
and 2 indicates the number of decimal digits.
[Description:]
When setting
C01
is linear, “-----” is displayed and
setting is not possible.
The setting range varies with the
C01
and
C02
setting.
A setting between 0 and 2 can be made when
C01
is
set to: 5, 15, 65 to 69, 97 to 101 and
C02
is set to 0.
C01
settings: 66, 68, 69, 98, 100, 101 and
C02
is set
to 1.
A setting of 0 and 1 can be made when
C01
is set to: 0
to 4, 6 to 14, 16, 64, 70, 71, 96, 102, 103 and
C02
is
set to 0.
C01
settings: 0 to 5, 7, 8, 10, 12 to 14, 16, 64, 65, 67,
70, 71, 96, 97, 99, 102, 103 and
C02
is set to 1.
Only a setting of 0 is possible when
C01
is set to: 6, 9,
11 and
C02
is set to 1
When the
C01
setting is for a t/c or RTD, this setting is
reflected in PVU (PV1) units.
-1.0 to +1.0
[Description:]
C01
settings for t/c and RTD display “-----” and setting is
not possible.
Use 0.0 for normal settings.
0: Celsius
1: Fahrenheit
[Description:]
When setting
C01
is linear, “-----” is displayed and
setting is not possible.
Chapter 7. PARAMETER SETUP