Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
PA 03
Unused3 [Description:]
“-----”is displayed and setting is not possible.
–
PA 04
Unused4–
PA 05
Program auto load*5 1: ON
2: OFF
0
PA 06
Unused6 [Description:]
“-----”is displayed and setting is not possible.
–
PA 07
Unused7–
PA 08
Auto-tuning8
0: AT not performed
1: Standard AT performed on currently used PID group
in mode other than READY mode.
2: AT writing overshoot-proof PID values to currently
used PID groups in mode other than READY mode
performed.
3: Standard AT performed on PID groups A1 to A7 in
READY mode.
4: AT writing overshoot-proof PID values to PID groups
A1 to A7 in READY mode continuously performed.
0
PA 09
Auto-tuning MV lower limit9 –5.0% to upper limit
[Description:]
Valid when setup data
C21
setting is set to 1, 3, 5.
0.0
PA 10
Auto-tuning MV upper limit10 Lower limit to +105%
[Description:]
Valid when setup data
C21
setting is set to 1, 3, 5.
100.0
PA 11
SP bias11 –10000 to +10000 SPU0 SPU
PA 12
PV1 digital filter12 0.0 to 120.0sec0.0
PA 13
PV1 bias13 –1000 to +1000 PVU (PV1)0 PVU
PA 14
Manipulated variable deviation limit
14 0.1 to 110.0% OUT/0.1sec110.0
PA 15
Time proportional output cycle
15 1 to 240sec10
PA 16
On-off control differential16 0 to +1000 SPU50 SPU
PA 17
PID computation initialize manipulated variable
17 –5.0 to +105.0%
[Description:]
“-----”is displayed and setting is not possible.
0.0
PA 18
Unused18 -----
PA 19
Unused19 -----
PA 20
Unused20 -----
PA 21
Unused21 -----
PA 22
PV2 digital filter22 0.0 to 120.0sec
[Description:]
“-----”is displayed and setting is not possible on model
with one PV input channel.
0.0
PA 23
PV2 bias23
–1000 to +1000 PVU (PV2)
[Description:]
“-----”is displayed and setting is not possible on model
with one PV input channel.
0 PVU
PA 02
Memory protect2
0: Disabled
1: Program settings are protected
2: Setup, variable parameters and event configurations
are protected.
3: Setup, variable parameters and event configurations
are protected.
4: Setup, variable parameters and event configurations
are protected.
5: Program settings and all parameter settings are
protected.
[Description:]
PA02
can be displayed and changed regardless of
PA01
and
PA02
settings.
0
PA 01
Keylock1
0: Keylock disabled
1: Display of setup data settings disabled
2: Display of all settings disabled
3: Display of all settings disabled. Operation keys disabled
[Description:]
PA01
can be displayed and changed regardless of
PA01
and
PA02
settings.
0
* : This function is available on the DCP551A***** model only.