EasyManuals Logo

Azbil dcp551 mark II User Manual

Azbil dcp551 mark II
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #111 background imageLoading...
Page #111 background image
7-5
Variable parameter setting
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
PA 03
Unused3 [Description:]
“-----”is displayed and setting is not possible.
PA 04
Unused4–
PA 05
Program auto load*5 1: ON
2: OFF
0
PA 06
Unused6 [Description:]
“-----”is displayed and setting is not possible.
PA 07
Unused7–
PA 08
Auto-tuning8
0: AT not performed
1: Standard AT performed on currently used PID group
in mode other than READY mode.
2: AT writing overshoot-proof PID values to currently
used PID groups in mode other than READY mode
performed.
3: Standard AT performed on PID groups A1 to A7 in
READY mode.
4: AT writing overshoot-proof PID values to PID groups
A1 to A7 in READY mode continuously performed.
0
PA 09
Auto-tuning MV lower limit9 –5.0% to upper limit
[Description:]
Valid when setup data
C21
setting is set to 1, 3, 5.
0.0
PA 10
Auto-tuning MV upper limit10 Lower limit to +105%
[Description:]
Valid when setup data
C21
setting is set to 1, 3, 5.
100.0
PA 11
SP bias11 –10000 to +10000 SPU0 SPU
PA 12
PV1 digital filter12 0.0 to 120.0sec0.0
PA 13
PV1 bias13 –1000 to +1000 PVU (PV1)0 PVU
PA 14
Manipulated variable deviation limit
14 0.1 to 110.0% OUT/0.1sec110.0
PA 15
Time proportional output cycle
15 1 to 240sec10
PA 16
On-off control differential16 0 to +1000 SPU50 SPU
PA 17
PID computation initialize manipulated variable
17 –5.0 to +105.0%
[Description:]
“-----”is displayed and setting is not possible.
0.0
PA 18
Unused18 -----
PA 19
Unused19 -----
PA 20
Unused20 -----
PA 21
Unused21 -----
PA 22
PV2 digital filter22 0.0 to 120.0sec
[Description:]
“-----”is displayed and setting is not possible on model
with one PV input channel.
0.0
PA 23
PV2 bias23
–1000 to +1000 PVU (PV2)
[Description:]
“-----”is displayed and setting is not possible on model
with one PV input channel.
0 PVU
PA 02
Memory protect2
0: Disabled
1: Program settings are protected
2: Setup, variable parameters and event configurations
are protected.
3: Setup, variable parameters and event configurations
are protected.
4: Setup, variable parameters and event configurations
are protected.
5: Program settings and all parameter settings are
protected.
[Description:]
PA02
can be displayed and changed regardless of
PA01
and
PA02
settings.
0
PA 01
Keylock1
0: Keylock disabled
1: Display of setup data settings disabled
2: Display of all settings disabled
3: Display of all settings disabled. Operation keys disabled
[Description:]
PA01
can be displayed and changed regardless of
PA01
and
PA02
settings.
0
* : This function is available on the DCP551A***** model only.
Chapter 7. PARAMETER SETUP

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Azbil dcp551 mark II and is the answer not in the manual?

Azbil dcp551 mark II Specifications

General IconGeneral
BrandAzbil
Modeldcp551 mark II
CategoryController
LanguageEnglish

Related product manuals