100.0
P-1
1
Proportional band (PID group 1)
0
I-1
2 Integral time (PID group 1)
0
d-1
3 Derivative time (PID group 1)
50.0
rE -1
4 Manual reset (PID group 1)
0.0
oL-1
5
Manipulated variable lower limit (Output limiter group 1)
100.0
oH-1
6
Manipulated variable upper limit (Output limiter group 1)
100.0
P-2
7
Proportional band (PID group 2)
0
I-2
8 Integral time (PID group 2)
0
d-2
9 Derivative time (PID group 2)
50.0
rE-2
10 Manual reset (PID group 2)
0.0
oL-2
11
Manipulated variable lower limit 
(Output limiter group 2)
100.0
oH-2
12
Manipulated variable upper limit 
(Output limiter group 2)
100.0
P-3
13
Proportional band (PID group 3)
0
I-3
14 Integral time (PID group 3)
0
50.0
d-3
15 Derivative time (PID group 3)
rE-3
16 Manual reset (PID group 3)
0.0
oL-3
17
Manipulated variable lower limit 
(Output limiter group 3)
100.0
oH-3
18
Manipulated variable upper limit 
(Output limiter group 3)
100.0
P-4
19
Proportional band (PID group 4)
0
I-4
20 Integral time (PID group 4)
0
d-4
21 Derivative time (PID group 4)
50.0
rE-4
22 Manual reset (PID group 4)
0.0
oL-4
23
Manipulated variable lower limit (Output limiter group 4)
100.0
oH-4
24
Manipulated variable upper limit (Output limiter group 4)
100.0
P-5
25
Proportional band (PID group 5)
0
I-5
26 Integral time (PID group 5)
0
d-5
27 Derivative time (PID group 5)
50.0
rE-5
28 Manual reset (PID group 5)
0.0
oL-5
29
Manipulated variable lower limit (Output limiter group 5)
100.0
oH-5
30
Manipulated variable upper limit (Output limiter group 5)
100.0
P-6
31
Proportional band (PID group 6)
0
I-6
32 Integral time (PID group 6)
0
d-6
33 Derivative time (PID group 6)
: 0.0 to 1000.0%
  ON-OFF control when set to 0.0
: 0 to 3600sec
  No integral operation when set to 0
: 0 to 1200sec
  No derivative operation when set to 0
: 0.0 to 100.0%
: -5.0 to manipulated variable upper limit %
: Manipulated variable lower limit to +105.0%
: -19999 to +20000 SPU
: -19999 to +20000 SPU 
Item code
Item
No.
User 
settings
Settings and descriptions
Factory default 
settings
P
l
d
rE
oL
oH
CP
tP
[Description:]
    When 
P
 is set to 0.0, ON-OFF control is on and 
l
, 
d
 and 
rE
 
settings display “-----” and setting is not possible.
    When the 
l
 setting is not equal to 0, “-----” is displayed for 
rE
 
and setting is not possible.
    Although a low 
P
 setting improves control, overshoot and 
hunting is more likely to occur.
    Although a low 
l
 setting improves tracking, cycling caused 
by integral operation occurs more often.
    Although a low 
d
 setting makes it easier to suppress 
overshoot, hunting is more likely to occur due to reactions to 
minute PV action. In normal temperature control, 
derivative time should be between 1/3 to 1/4 of the integral 
time. Since derivative operation is a cause of hunting in 
pressure and flow control, set 
d
 to 0.0 to turn off derivative 
action or set a low value.
    The 
rE
 setting is used to eliminate offset caused by 
proportional action (no integral action) and sets a suitable 
deviation of 0.
    The 
oL
 and 
oH
 settings also operate as integral limiters. 
When 
oL
 or 
oH
 manipulated variable reaches the upper or 
lower limit, they turn off integral action and prevents reset 
windup that occurs when PV has not risen for a long time.
    The 
CP
 setting is the point where switching occurs between 
PID groups A1 to A7.
 
tP
 is the tuning point where 
P
, 
I
 and 
D
 settings in groups A1 
to A7 are automatically tuned starting from A1.