EasyManuals Logo

Azbil dcp551 mark II User Manual

Azbil dcp551 mark II
220 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #119 background imageLoading...
Page #119 background image
7-13
Settings by event type
For information on event operations, see “ Events(pages 5-5 to 5-15).
Event type 0 2 31
Meaning
Message
Event off
OFF
PV upper limit
PV-H
PV lower limit
PV-L
Time event
TIME
Range of auxiliary
setting 1
Message
Unused Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Unused
Range of auxiliary
setting 2
Message
Unused Unused UnusedUnused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
Time type
Event type 4 6 75
Meaning
Message
Upper deviation limit
DEV-H
Deviation rate upper limit
wait DEV-H-W
Deviation lower limit with
stanby DEV-L-W
Lower deviation limitt
DEV-L
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused Unused UnusedUnused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Event type 8 10 119
Meaning
Message
Absolute value deviation
upper limit A-DEV-H
Absolute value deviation rate upper
limit with stanby A-DEV-H-W
Absolute value deviation lower limit
with stanby A-DEV-L-W
Absolute value deviation
lower limit A-DEV-L
Range of auxiliary
setting 1
Message
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Range of auxiliary
setting 2
Message
Unused Unused UnusedUnused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Event type 12 14 1513
Meaning
Message
PV deviation rate upper
limit A-DEV-H
SP
upper limit
SP-H
SP lower limit
SP-L
PV deviation rate lower
limit D-PV-L
Range of auxiliary
setting 1
Message
Sampling cycle 0.1 to
600.0sec
sampling rate
Hysteresis
0 to 1000 SPU
hysteresis
Hysteresis
0 to 1000 SPU
hysteresis
Sampling cycle 0.1 to
600.0sec
sampling rate
Range of auxiliary
setting 2
Message
Unused Unused UnusedUnused
Setting category
Operation category
Segment type
PV type
Segment type
PV type
Segment type
PV type
Segment type
PV type
Chapter 7. PARAMETER SETUP