Loading...
10-7
PID group, output limiter group number items cannot be displayed with and keys
G.SOAK items, PV shift items and repeat items cannot be displayed with and keys
PV start items, cycle items and pattern link items cannot be displayed with and keys
Segment insertion and deletion cannot be confirmed with FUNC and ENTER keys
Program deletion cannot be confirmed with FUNC and ENTER keys during pattern item
registration
Cause Measure
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Cause Measure
Set to memory protect. Set variable parameter
PA02
to 0, 2 or 4.
Program being set is running (in RUN,
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG +
RUN/HOLD keys).
Not set to pattern item on programming map. Move to the pattern item on the programming map.
This segment is not set on the programming
map.
Move to a set segment or set the segment.
Cause Measure
Programming item display off Set setup data
C60
to 0.
Cause Measure
Programming item display off Set setup data
C59
to 0.
Cause Measure
Programmer function on Set setup data
C21
to something other than 0.
Programming item display off Set setup data
C58
to 0.
Chapter 10. MAINTENANCE AND TROUBLESHOOTING