10-7
● PID group, output limiter group number items cannot be displayed with  and  keys
● G.SOAK items, PV shift items and repeat items cannot be displayed with  and  keys
● PV start items, cycle items and pattern link items cannot be displayed with  and  keys
● Segment insertion and deletion cannot be confirmed with FUNC and ENTER keys
● Program deletion cannot be confirmed with FUNC and ENTER keys during pattern item
registration
Cause Measure
Program being set is running (in RUN, 
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG + 
RUN/HOLD keys).
Cause Measure
Set to memory protect. Set variable parameter 
PA02
 to 0, 2 or 4.
Program being set is running (in RUN, 
HOLD, FAST, END, READY FAST).
Set READY mode to execute RESET operation (PROG + 
RUN/HOLD keys).
Not set to pattern item on programming map. Move to the pattern item on the programming map.
This segment is not set on the programming 
map.
Move to a set segment or set the segment.
Cause Measure
Programming item display off Set setup data 
C60
 to 0.
Cause Measure
Programming item display off Set setup data 
C59
 to 0.
Cause Measure
Programmer function on Set setup data 
C21
 to something other than 0.
Programming item display off Set setup data 
C58
 to 0.
Chapter 10.  MAINTENANCE AND TROUBLESHOOTING