7-24
0: Continues until power is turned off
1: PV1
2: PV2
3: High-temperature PV
4: Low-temperature PV
[Description:]
“-----” is displayed and setting is not possible on model with
one PV input channel.
When
C25
is set to more than 1, “-----” is displayed and
setting is not possible.
When
C26
is set 0, “-----” is displayed and setting is not
possible.
0
C
29
29
Selections available when
power is on during PV
channel switching
1 to 1000 PVU (PV1)
[Description:]
“-----” is displayed and setting is not possible on model with
one PV input channel.
When
C25
is set to more than 1, “-----” is displayed and
setting is not possible.
When
C26
is set 0, “-----” is displayed and setting is not
possible.
100 PVU
C 28
28
PV channel switching dead
band
0: No
1: PV1 only
2: PV2 only
3: PV1 and PV2
[Description:]
The range of settings is 0 to 1 on model with one PV
input channel.
0
C
30
30
PV equalizer
0: READY mode
1: END mode
0
C
31
31
End of operation
0: No
1: Yes
0
C
33
33
Manipulated variable setting
in PV overrange
-5.0 to +105.0 %
0.0
C
34
34
Manipulated variable in PV
overrange
0: smooth
1: preset
[Description:]
When
C21
is set to 0, the output is smooth regardless of
setting.
0
C
35
35
Manual change mode
–5.0 to +105.0 %
0.0
C
36
36
Preset MANUAL value
[Description:]
“-----” is displayed and setting is not possible.
----
C
37
37
Unused
----
C
38
38
Unused
----
C
39
39
Unused
----
C
40
40
Unused
----
C
41
41
Unused
----
C
42
42
Unused
0 to 3600sec
When set to 0, operation continues regardless of outage time.
[Description:]
The HOLD mode is invoked when the outage is longer than set time.
The measurement of a power outage may vary by about 10 seconds.
0
C
43
43
Length of outage permitting
continuous operation
[Description:]
“-----” is displayed and setting is not possible.
----
C
44
44
Unused
0: SP
1: PV
2: Deviation (DEV)
3: Manipulated variable (MV)
4: PV1
5: PV2
[Description:]
“-----” is displayed and setting is not possible on model
without auxiliary output.
0
C
45
45
Auxiliary output 1 type
-19999 to +20000 SPU (
C45
not equal to 3)
-1999.9 to +2000.0 SPU (
C45
set to 3)
[Description:]
“-----” is displayed and setting is not possible on model
without auxiliary output.
0 SPU
C
46
46
Auxiliary output 1 lower limit
(4mA)
10000SPU
C
47
47
Auxiliary output 1 upper limit
(20mA)
-5.0 to +105.0 %
0.0
C
32
32
Manipulated variable in READY mode
Item code
Item
No.
User
settings
Settings and descriptions
Factory default
settings
Chapter 7. PARAMETER SETUP