8-22
The set value of the inserted segment is as follows:
Set SP value : same value as the original segment before insertion
Set time value : 0:10, 1.0
Event items, PID groups, output limiter group number items, G.SOAK items, PV
shift items and repeat items are not set.
Then the 99th segment has already been set, the segment insertion indication
InS.” is not displayed.
When 2000 segments have already been set, pressing the ENTER key to
execute an insertion cannot be used to insert a segment.
When segments are deleted, the following segments are moved up and the
numbers of subsequent segments are decremented by one. When the final
segment is deleted, the displayed segment becomes an unset segment.
•A program that is running (in RUN, HOLD, FAST, END or READY FAST
mode) cannot be deleted.